VRF Outdoor Units (VRF Heat Pump)

Micro Heat Pump VRF Outdoor Unit

Features

Nominal horse power6HP
Power source1 Phase 220-240V, 50Hz
Starting currentA5
Max CurrentA28
Nominal capacityCoolingkW15.5
Heating15.5
Electrical characteristics
Power Consumption
CoolingkW5.20
Heating4.28
Exterior dimensionsHxWxDmm845x970x370
Sound pressure levelCooling/HeatingdB(A)54/57
Net Weightkg85
RefrigerantType / GWPR410A / 2088
RefrigerantChargekg/TCO2Eq5.0 / 10.44
Refrigerant piping sizeLiquid linemm(in)ø9.52(3/8")
Refrigerant piping sizeGas linemm(in)ø15.88(5/8")
Capacity connection%80~150
Number of connectable indoor units10 *
SEER / SCOP (Outdoor unit)7.21 / 4.55
The data are measured under the following conditions(ISO-T1).
Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
[ ] : Pipe sizes applicable to European installations are shown in parentheses.

Schematic

vrf-image