VRF Outdoor Units (Heat Recovery)
Standard Heat Recovery VRF Outdoor Unit
| Nominal horse power | 12HP | |||
| Power source | 3 Phase 380-415V, 50Hz | |||
| Starting current | A | 5 | ||
| Max Current | A | 21.2 | ||
| Nominal capacity | Cooling | kW | 33.5 | |
| Heating | 33.5 | |||
| Electrical characteristics Power Consumption | Cooling | kW | 9.65 | |
| Heating | 8.44 | |||
| Exterior dimensions | HxWxD | mm | 1697x1350x720 | |
| Sound pressure level | Cooling/Heating | dB(A) | 63/64 | |
| Net Weight | kg | 305 | ||
| Refrigerant | Type / GWP | R410A / 2088 | ||
| Refrigerant | Charge | kg/TCO2Eq | 11.5 / 24.012 | |
| Refrigerant piping size | Liquid line | mm(in) | ø12.7(1/2”) | |
| Refrigerant piping size | Suction Gas line | mm(in) | ø25.4(1”) [ø22.22(7/8")] | |
| Refrigerant piping size | Discharge Gas line | mm(in) | ø19.05(3/4”) | |
| Capacity connection | % | 50~200 | ||
| Number of connectable indoor units | 44 | |||