VRF Indoor Units (4 WAY CEILING CASSETTE)

Ceiling Cassette VRF Indoor Unit

Features

Nominal cooling capacitykW16.0
Nominal heating capacitykW18.0
Power source1 Phase 220-240V 50Hz / 220V 60Hz
Power consumptionCoolingkW0.14-0.14
HeatingkW0.14-0.14
Sound power leveldB(A)66
Sound pressure level Coolingdb(A)P-Hi:49 Hi:42 Me:39 Lo:33
Exterior dimensions unitH x W x DmmUnit:298x840x840
Exterior dimensions panelH x W x DmmPanel:35x950x950
Net weightkgUnit:25 Standard Panel:5
Air flowm3/minP-Hi:38 Hi:29 Me:26 Lo:19
Outside air intakePossible
PanelFine Snow: (Standard, T-PSA-5BW-E) (Draft prevention,T-PSAE-5BW-E) | Shadow Black: (Standard, T-PSA-5BB-E) (Draft prevention, T-PSAE-5BB-E)
Air filter, Q'tyPocket Plastic net x1 (Washable)
Remote control(option)wired: RC-EX3A, RC-E5, RCH-3, wireless: White: RCN-T-5BW-E2 | Black: RCN-T-5BB-E2
Refrigerant pipe connection (liquid / gas)mm(in)Liquid line:ø9.52(3/8") Gas line:ø15.88(5/8")
RefrigerantType/GWPR410A / 2088
The data are measured under the following conditions(ISO-T1).
Cooling: Indoor temp. of 27°CDB, 19oCWB, and outdoor temp. of 35°CDB.
Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.
External static pressure of indoor unit is 10Pa.
The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions.

Schematic

vrf-image
mhi-bizeulasin