VRF Indoor Units (1 WAY CEILING CASSETTE)
Ceiling Cassette VRF Indoor Unit
| Nominal cooling capacity | kW | 7.1 | ||
| Nominal heating capacity | kW | 8.0 | ||
| Power source | 1 Phase 220-240V, 50Hz | |||
| Power consumption | Cooling | kW | 0.09-0.09 | |
| Heating | kW | 0.09-0.09 | ||
| Sound power level | dB(A) | 61 | ||
| Sound pressure level Cooling | db(A) | P-Hi:49 Hi:46 Me:41 Lo:36 | ||
| Exterior dimensions unit | H x W x D | mm | Unit:220x1150x565 Panel:35x1250x650 | |
| Net weight | kg | Unit:28 Panel:5 | ||
| Air flow | m3/min | P-Hi:17 Hi:15 Me:12 Lo:9.5 | ||
| Outside air intake | Possible | |||
| Panel | TS-PSA-3AW-E | |||
| Air filter, Q'ty | Pocket Plastic net x2 (Washable) | |||
| Remote control(option) | wired:RC-EX3A, RC-E5, RCH-E3 wireless:RCN-TS-E2 | |||
| Refrigerant pipe connection (liquid / gas) | mm(in) | Liquid line:ø9.52(3/8") Gas line:ø15.88(5/8") | ||
| Refrigerant | Type/GWP | R410A / 2088 | ||